Transformer excitation inrush, single listening to this name feels very complicated

What is the transformer excitation inrush

Transformer excitation inrush, single listening to this name feels very complicated, it also has another name “closing inrush”, is the transformer in the no-load closing moment, that is, just started to work or re-connect to the power supply, its windings suddenly produce a large current phenomenon. In layman's terms, just like our high-power electrical appliances (such as air conditioning) in the start-up, due to the internal coils and magnets and other components of the equipment need to quickly reach the working state, will temporarily consume a large amount of current. Transformer excitation inrush current works on a similar principle, except that it occurs in the core and windings of the transformer. This current is a special current phenomenon during the initial period when the transformer is put into operation.
Reasons for transformer excitation inrush current

Superposition of residual flux and operating flux
We know that the transformer core itself is magnetically conductive, and there is a hysteresis property within the core material, that is, under the action of an alternating magnetic field, the core will produce a process of magnetization and demagnetization. Before the transformer is put into operation, there may be residual magnetic flux in its core. What is residual flux?
Residual flux is the magnetic flux that remains in the transformer core and coils when the AC power supply is interrupted. This is because during normal operation of the transformer, the iron core is magnetized, and when the power supply is cut off, the magnetization does not disappear immediately, but retains a portion of the magnetic flux.
When the transformer is put into operation, the flux generated by the operating voltage and the residual flux in the core are in the same direction, and the two are superimposed, resulting in a total flux that far exceeds the saturation flux of the core.

 

Figure Source Electrical Applications
Core saturation
If the total superimposed magnetic flux exceeds the maximum value that the core can handle (saturation flux), the core will act as if it is “full” and will not be able to absorb any more magnetic flux. At this point, a very large current will be generated, that is, the excitation inrush current.
The size of the excitation inrush current is also related to the value of the supply voltage and the initial phase angle, the value of the core flux and the direction of remanent magnetism before closing, the equivalent impedance value and phase angle of the system, the transformer winding wiring and neutral grounding, the magnetization characteristics of the core material, hysteresis characteristics, etc., the core structural type, the level of assembly process.
Transformer excitation inrush current characteristics

Peak value: The peak value of excitation inrush current can reach 6-8 times of the rated current of the transformer, or even higher. This means that at the moment of transformer startup, it may experience a very large current shock.
Fast decay: Although the peak of the excitation inrush current is large, it decays very quickly. The decay time for a large capacity transformer may be as long as 5-10 seconds, whereas for a small capacity transformer it may only take about 0.2 seconds.
Figure Source Electrical Applications
Contains Complex Components: The excitation inrush contains not only the normal AC current components, but also DC components and higher harmonic components. These components make the waveform of the excitation inrush complex.
Hazards of transformer excitation inrush

Excitation inrush currents can cause transformer core saturation and secondary side voltage bursts, resulting in a loss of transformer insulation and possible equipment failure.
The excitation inrush current may increase the temperature of the transformer core and generate eddy current losses in the winding conductors, tank walls and other metal components, leading to overheating of the transformer, aging of the insulation, and affecting the life of the transformer.
High-amplitude excitation inrush current will directly cause physical damage to the transformer and circuit breaker, and may even burn the equipment.
How to suppress transformer excitation inrush current

 

Suppressing the excitation inrush current is an important measure to ensure the stable operation of the transformer and power system, and the excitation inrush current of the transformer can be suppressed by the following measures:
1. Use the excitation motor: the excitation motor is a method of providing the steady state power to the transformer through its rotor. Since the excitation motor has the inertia of the rotor, it slows down the rate of rise of the excitation current.

2. Increasing the excitation resistance of the transformer: Adding a suitable resistance in the excitation circuit of the transformer can limit the rapid rise of the excitation current.

3. Introduce transformer anti-surge measures: by adding anti-surge circuits, such as reactors, capacitors, etc., to reduce the impact of excitation surge current on the equipment, effectively absorbing and consuming the surge current energy, to protect the transformer and the power grid safety.
4. Utilize the closing bias magnetism and transformer remanent magnetism to offset each other: by controlling the direction and size of the closing bias magnetism, make it offset each other with the transformer remanent magnetism to avoid transformer core saturation, so as to inhibit the generation of excitation inrush current.